LIS-0816 (8 Ways 16A Smart PDU)


No.

Item

Description

1

 

Defaults Switch

This switch is recessed and must be pushed with a thin object, such as the end of a paper clip

You can press this button and hold it for more than 3 seconds to reset the PDU to factory default values

Release this switch and restart the device to take effect.

2

Reset Switch

Hold down the key to restart the PDU

3

LCD Displays

LCD used to display PDU status information

4

Interface selection button

Used to control the MENU function of LCD

5

Power output socket 

Each power socket can connect to electrical devices with the current less than 10A. The total output power is less than 16A/32A. If the power output exceeds the maximum load, the PDU and electrical devices may be damaged and the circuit breaker protection function may be triggered

6

Cascade input port

Cascaded RJ45 input to other devices

 

7

Cascade output port

Cascaded output with other devices through RJ45

 

8

LAN Port

 

It can connect to 10M/100M Ethernet network.  Control and access PDUs

9

T/H sensor ports 

External temperature and humidity sensors can be connected through RJ11 ports

10

Overload protection switch  

When the PDU is overloaded, the protector automatically disconnects the power supply to protect the electrical equipment.

11

16A power input socket 

Please insert the power cable to the AC power supply here.  This power input socket is equipped with a switch setting. When the power cable is connected and the power switch is turned on, the PDU can be put into working state.

● Remote users can monitor PDU and loop status on web pages 
● Support safe shutdown function  
● Each device has its own power supply and socket.  The user interface can be accessed even when the overload state triggers the automatic power-off switch on this device  
● Fire surge protection, reduce the risk of fire caused by surge.  
● Remote power management via TCP/IP and built-in 10/100 Ethernet port
● Support network communication protocols: TCP/IP, UDP, HTTP, DHCP, 10BASE-T /100Base-TX,  Ping 
● Individual power sockets can be controlled locally and remotely (open, close, cycle switch)  
● Power on sequence - The user can set the power on sequence and the delay time for each socket so that the device can be turned on in the appropriate sequence  
● It can be easily set and operated through the browser interface  
● Support for multiple browsers (IE, Mozilla, Firefox, Chrome, Safari, Opera, Netscape)  
● It can measure the power status of the PDU loop of the whole power distributor  
● Current and voltage critical setting  
● Provides the socket naming function  
● Support activity log  
● Supports firmware upgrade  
● Support multiple languages: English, simplified Chinese  
● Configurable mail notification feature to keep your system notified of changes in status  
● Flexible mounting design for easy mounting on structured wiring enclosures, walls or behind tables and televisions.
● Supports SNMP management  
● The IP blacklist function effectively blocks malicious users  
● Support the current, power, and power factor detection of each power supply separately output port  
● Support separate port set threshold warning and power off Settings to protect the safety of electrical devices
● RTC supports timer operation in the absence of power supply  
● Support multi-user Settings, and multi-user different management rights Settings  
● Support PDU energy usage statistics, quickly understand the usage of electrical equipment through graphics
● PDU Exterior The PDU provides LCD Displays to visually display the operating status of ports and hosts  XXXIX. Dynamic password verification in the login window enhances user login security verification  
● You can add and query scheduled tasks to make work plans for PDU port sockets in advance  
● Displays current and voltage alarms on the home page, and queries historical records of PDU anomalies  
● Support zero meter clearing function
● Provides ports for the ambient T/H sensor
● Provides an RJ45 connector

Function

LIS-0816

LIS-0832

Power Outlets

Direct

8

 

 

Connectors

Power Inlet

IEC C19

Aviation connector

Power Outlets

IEC C13

LAN

1 x RJ-45(Female)

Cascade

2 x RJ-45(Female)

 

LED lamp

 

State of the socket

LCD Displays

Power

10/100M

1 (Orange/ Green)

Switches

Reset

1 x Semi-recessed button

Restore default Settings

1 x Semi-recessed button

I/P Rating

100–240V~;

50–60Hz;16A

Load Capacity

3840W

O/P Rating

Per Port

100–240V~; 50–60Hz; 10A

Total

100–240V~; 50–60Hz;

16A/32A

Environment

Operating Temperature

0–50

Storage Temperature

-20–60

Humidity

0–80% RH Non-condensing

Physical

Properties

Housing

Metal

Weight

2.42kg

Dimensions (L x W x H)

 

442*159*44.5mm